Two-motor sequence circuit with contactor enable

In a sequence circuit, a second drive depends on a defined condition of the first. Here M2 may remain energised only while contactor K1 is energised. This is an electrical contactor enable, not proof that motor M1 is rotating or supporting a process.

Structure and operation

Such dependencies can be useful where several drives must follow an intended start and shutdown order. The correct order is determined by the actual process. The example has separate K1/F1/M1 and K2/F2/M2 power branches. F3 and F4 are their short-circuit protective devices; F0 protects the shared 230 V control circuit.

Circuit diagram

Sequence circuit with two three-phase motorsSequence circuit with two three-phase motors
Both motors off · start M1 first

Enlarge diagram

Reading the example

S2 starts M1 and S1 stops it. K1 holds through auxiliary NO 13–14. Additional K1 NO contact 23–24 precedes the entire K2 start and holding area. S4 starts M2, S3 stops it, and K2 holds through its own 13–14. Because 23–24 also precedes K2 Hold, M2 cannot latch around the enable condition.

Connections and equipment selection

Stop M1 or overload F1 releases K1 and removes K2 enable, switching both drives off electrically. Stop M2 or overload F2 affects M2 only; M1 remains governed by its own holding state. PE remains unswitched at both housings. N supplies the control circuit and is not a motor-winding connection here.

Try the model

Compare the commands with the drawn electrical paths. The rotor motion is an additional illustration, not a measurement. Try the following states in the model.

  1. Briefly press S4 with M1 off: M2 does not start and no later start is queued.
  2. Start M1 with S2 and release it, then start M2 with S4. Each holds through its own contact.
  3. Press S3: M2 stops while M1 can continue.
  4. Press S1 or trip F1: both contactors release. Trip F2 separately and compare shutdown behaviour.
  5. Deliberately hold S4 before enabling M1: M2 can start when the maintained command becomes enabled.
  6. Compare supply loss and overload reset with Start buttons released or maintained.

An auxiliary NO contact follows the contactor mechanism. It measures neither shaft motion, airflow, flow rate nor pressure. Applications requiring a confirmed process condition need suitable sensors and matching control logic. Run-on, time delay and automatic restart are not implicit features of this simple circuit.

Benefits and limits

The dependency is clear in the diagram while both motor branches remain individually controllable. This simple enable is not complete process monitoring. The rotors and coasting are illustrative; they confirm neither attainable speed nor a safe stopping time.

The model explains a functional example. Real installation work requires appropriate competence, authorisation and safe working procedures; normal Stop is not safe isolation. Functional testing and electrical safety verification remain separate.

Questions about the example

Why not use K1 13–14 for both tasks?

In this example 13–14 holds the first motor command. A separate additional NO contact 23–24 makes the enable before the second start/holding area explicit.

Does M2 start automatically when M1 starts?

Not with S4 released. A maintained S4 command can become effective when K1 provides enable.

Does K1 enable prove that M1 is running?

No. Contactor position and actual motor or process state are different information.

Related explanations

Sources and equipment documents

Further context: Relays and contactors · Functional testing · Timer switch with contactor

Electrical safety: scope, competence and precautions

Put electrical safety first.

  • These explanations and simplified diagrams support learning. They are not complete installation designs, site-specific risk assessments or a substitute for competent professional assessment.

  • Electrical work can be life-threatening. It requires the competence and authorisation appropriate to the actual task, installation and jurisdiction.

  • Errors and omissions can occur. Check the actual equipment documentation, applicable requirements and the complete installation before relying on an example; a working device is not proof of electrical safety.

  • Personal protective equipment must suit the assessed hazards and task. It does not replace isolation, appropriate tools, competence or a safe system of work.

  • Do not work on exposed live parts on the basis of these guides. Identify every relevant source, isolate it, secure against reconnection and prove dead using suitable equipment and procedures before access.

  • Responsibilities for design, installation and verification must be established for the actual work. A website statement does not determine liability or remove duties under applicable law.

  • This summary is not exhaustive. Where the circuit, condition or protective arrangement is uncertain, obtain suitable professional assistance before work proceeds.

  • Complete the required inspection, testing and documentation before use, and maintain the installation and equipment appropriately.

Read more

Electrical terms explained

Electric current

The rate of flow of electric charge, measured in amperes (A). Conventional current direction follows positive charge flow, which is opposite to electron drift in a metallic conductor.

Voltage

The electric potential difference between two points, measured in volts (V). Always identify the reference points, such as line-to-neutral or line-to-earth; a voltage is not a property of one isolated terminal alone.

Resistance

The opposition associated with resistive current flow, measured in ohms (Ω). For a component behaving as an ohmic resistance under the stated conditions, U = IR.

Electrical power

The rate of electrical energy transfer, measured in watts (W). P = UI applies to steady DC; in a sinusoidal single-phase AC circuit, active power is UI cos φ using RMS values. The general average depends on voltage and current waveforms.

Ohm's law

For an ohmic resistance, current is proportional to the applied voltage: I = U/R. Resistance can vary with temperature, and non-linear devices do not necessarily obey one constant-resistance relationship.

Kirchhoff's laws

The current law expresses charge conservation at a circuit node. The voltage law states that the algebraic sum of voltages around a closed loop is zero within the applicable circuit model; induced effects must be represented appropriately.

Direct current (DC)

Current that maintains one direction. Its magnitude may be constant or vary; pulsating DC is still distinguished from current that reverses direction.

Alternating current (AC)

Current whose direction reverses with time, commonly periodically. Public supplies normally use approximately sinusoidal AC, while electronic equipment can produce other waveforms.

Frequency

The number of cycles per second of a periodic quantity, measured in hertz (Hz). Many European public supplies operate at a nominal 50 Hz.

Phase difference

The relative position of periodic quantities of the same frequency, often expressed in degrees or radians. For sinusoidal quantities, a time displacement can be related to that phase angle.

Circuit diagram

A drawing representing circuit components and their electrical connections using symbols. It is distinct from a physical layout or a complete installation design.

Capacitor

A component that stores energy in an electric field. Its capacitance relates stored charge to voltage under the stated conditions; a practical capacitor also has voltage, current and other operating limits.

Strappers in lighting circuits

The pair of conductors linking the changeover contacts in conventional two-way lighting switching, including intermediate switching where used. They carry the alternative switching paths and are not transformer windings; identify their actual functions from the circuit.

Coil or winding

A conductor arranged in turns, commonly to produce magnetic effects. Its behaviour includes inductance as well as the resistance and other properties of the actual winding.

Inductance

The relationship between flux linkage and current in the applicable model, measured in henries (H). Changing current produces an induced voltage; for a constant inductance its magnitude relates to L di/dt with the appropriate sign convention.

Capacitance

The relationship between stored charge and voltage, measured in farads (F). For a constant capacitance, changing voltage produces current according to i = C dv/dt.

Transistor

A semiconductor device used for switching, amplification or other control functions. Its operating principle and control quantities depend on whether it is, for example, a bipolar transistor or a field-effect device.

Semiconductor

A material whose electrical behaviour can be controlled through composition, electric fields, light or other conditions. Semiconductor devices use this behaviour for functions such as rectification, switching and amplification.

Diode

A device with a strongly directional current-voltage characteristic. Real diodes have forward losses, reverse leakage and limits; they do not act as perfect one-way valves at every voltage.

Relay

A device that changes an output in response to a control input. An electromechanical relay uses a coil and contacts, while a solid-state relay uses electronic switching elements.

Switch

A device that makes, breaks or changes electrical connections. Its rating, contact arrangement and permitted duty determine the applications for which it is suitable.

Electrical network

An interconnection of electrical components and branches. Series, parallel and more complex arrangements can be analysed with an appropriate circuit model.

Transformer

A device transferring energy between magnetically coupled windings through changing flux. Turns ratio influences voltage and current relationships; losses, limits and any conductive connection depend on its construction.

Electromagnet

A magnetic arrangement energised by electric current, commonly using a coil and magnetic core. Contactors, relays and actuators use electromagnetic force for mechanical operation.

Impedance

The relationship between voltage and current phasors in a sinusoidal steady-state model, measured in ohms. It combines resistance and reactance and can vary with frequency.

Short circuit

An unintended low-impedance connection between points at different potentials. Current is limited by the complete source and fault-path impedance, not literally unrestricted.

Electric circuit

An arrangement of sources, conductors and components. Current flows where a complete conductive path exists, although a circuit can also be described in an open or disconnected state.

Series connection

Components in one unbranched path carry the same current. Their voltages add algebraically; the individual voltage shares depend on their electrical behaviour.

Parallel connection

Branches connected between the same two nodes share the same voltage. The branch currents depend on their loads and add algebraically at the connection points.

Fuse

An overcurrent protective device with an element designed to melt and interrupt the circuit under specified conditions. Its rating, characteristic and breaking capacity must suit the application.

Overcurrent protection

Protection against overload and short-circuit effects, commonly using fuses or circuit-breakers. A sensing relay may require a separate interrupting device; an ordinary RCCB does not provide this protection by itself.

Earthing

A deliberate connection of a system point or conductive part to earth. Protective earthing forms part of an electric-shock protection arrangement; it must not be confused with neutral, functional earth or a guarantee of zero touch voltage.

Frequency converter or variable-speed drive

Electronic equipment that produces a controlled output frequency, commonly with controlled voltage, to operate a suitable motor. Its pulsed output, protection and compatibility requirements differ from a direct mains supply.

Electromagnetic compatibility (EMC)

The ability of equipment to operate satisfactorily in its electromagnetic environment without causing unacceptable disturbance to other equipment. Both emissions and immunity matter.

Power loss

Energy dissipated per unit time, commonly as heat in conductors, cores, insulation or semiconductor devices. Ideal inductors and capacitors exchange stored energy without average loss; practical components have additional loss mechanisms.

Short-circuit current

The current resulting from a short circuit. Prospective fault current is assessed to select protective devices with adequate interrupting capability and to check thermal and mechanical effects.

Power factor

The ratio of active power to apparent power. For sinusoidal voltage and current it equals cos φ; with distortion it also reflects waveform effects. It is not the same as energy-conversion efficiency.

Insulation resistance

Resistance measured between specified conductive parts separated by insulation under stated test conditions. The test voltage, connected equipment and interpretation must suit the circuit; it is not a complete assessment of insulation performance on its own.

Further information